Bpanelboard arranged in horizontal configuration w/enclosure back as bottom side and include hinged cover on topside, weatherproofed, circuit breakers to be 3-pole w/interrupting ratingsat 480v ac in accordance w/fed-spec w-c-375a amend 4, be classes and trip ratings connected to 3-phase, 1200ampere bus bar, cl 2f 100 amp trip-2 ea, cl 3b 225 amp trip-6 ea, cl 4b 400 amp non-automatic trip-4 ea, conduit bushings to be two-piece insulating conforming to type 3, cl 1, kind r, fed-spec w-c-408b in sizes and quantities, 2 in-2 ea f/10 amp circuit breaker conductor, 3 in-6 ea f/225 amp circuit breaker conductor, 4 in-4 ea f/400 amp circuitbreaker conductor, conduit bushings installed in enclosure bottom side in relative location to circuit breakers they are to be utilized, 1 ground terminal w/solderless lug, solderless lug shall be compatible w/aluminum and copper and have the capacity f/1 no. 6-awg copper conductor, conforms to porta-power pac inc, dwg no. 105100 or equal
NSN 5999-00-156-4424
NSN 6145-01-634-0388
NSN 5965-01-278-8218
NSN 6105-01-567-0810
NSN 5895-00-470-8276
NSN 5975-01-383-9449
NSN 6130-01-219-9065
NSN 5920-01-337-3823
NSN 5930-01-089-5335
NSN 6240-00-543-9321
NSN 6685-00-081-3529
NSN 5935-01-273-3142